Products

ZWKC-GA Circuit Breaker Analyzer

  • Large 9-inch color screen
  • It can simultaneously measure 12 metal contact fractures, 6 main fractures, 6 auxiliary fractures, and 1 speed (3 speeds are optional).
  • High-speed thermal printer, convenient for on-site printing of test data.
  • Equipped with linear sensor, rotation sensor, universal sensor, laser sensor (optional), bracket, special fixed multifunctional joint, installation is extremely convenient and simple.

Company Profile

The company specializes in the research anddevelopment, production, sales, and service of electric power systemautomation testing equipment, providing customers with one-stopservices.

Product Introduction

With the development of society, people have higher and higher requirements for the safety and reliability of electricity use. High-voltage circuit breakers are responsible for the dual tasks of control and protection in the power system, and their performance is directly related to the safe operation of the power system. The mechanical characteristic parameter is one of the important parameters to judge the performance of the circuit breaker. The ZWKC-GA high-voltage switch characteristic comprehensive tester (high-voltage switch mechanical characteristic tester) is based on the latest “High-voltage AC Circuit Breaker” GB1984-2003 as the design blueprint, and refers to the People’s Republic of China Electric Power Industry Standard “General Technical Requirements for High Voltage Test Equipment” 》Part 3, DL/T846.3-2017 is the design basis, which provides convenience for the dynamic analysis of various circuit breakers, and can accurately measure various voltage levels of less oil, more oil, vacuum, and sulfur hexafluoride The mechanical dynamic characteristic parameters of high-voltage circuit breakers. High-voltage circuit breakers are responsible for the dual tasks of control and protection in the power system, and their performance is directly related to the safe operation of the power system. The mechanical characteristic parameter is one of the important parameters to judge the performance of the circuit breaker.

Functional Characteristics

1. This instrument is an embedded industrial computer, the main board is based on CortexTM-A8, the main frequency is 1GHZ, the flash memory is 1GB, and the boot speed is only 16 seconds. Large 9-inch color screen, windows operating system, intuitive user-friendly operation interface, touch screen, support Chinese and English input, which is convenient for on-site operators.
2. High-speed thermal printer, convenient for on-site printing of test data.
3. The integrated operating power supply in the machine eliminates the need for on-site secondary power supply, which is convenient and quick to use. It can provide DC6~270V adjustable power supply, current 20A. The operating voltage value of the opening and closing coil can be set arbitrarily, and the low voltage operation test of the circuit breaker can be done.
4. Equipped with linear sensor, rotation sensor, universal sensor, laser sensor (optional), bracket, special fixed multifunctional joint, installation is extremely convenient and simple.
5. Suitable for all types of SF6 switches, GIS combination electrical appliances, vacuum switches, and oil switches produced at home and abroad.
6. The switch action once, get all the data and graphics, the test data and graphics are displayed on the same screen, and the speed can be recalculated without retesting.
7. The host can store 30000 groups of current test data (expandable memory card), and the real-time clock in the machine is convenient for archiving.
8. Equipped with 2 USB ports, which can be connected to the mouse to operate the instrument, and the data can be directly saved to the U disk, uploaded to the computer for analysis and storage. RS232 interface online operation (optional), WIFI operation optional.
9. At the same time, it can measure 12 metal contact fractures, 6 main fractures and 6 auxiliary fractures, and 1 speed (optional for 3 speeds).
10. Contains the envelope curve, through the value tested by a switch, the standard envelope curve is generated for analysis and comparison, and the switch vibration frequency analysis can also be carried out.
11. The internal anti-interference circuit can satisfy the reliable use in 500KV substation

Technical Parameter

Size ZWKC-GA
Time measurement 12 channels inherent opening (closing) time
Different periods in the opening (closing) phase
The difference between opening (closing) phases in different periods
Closing (opening) bounce time (bounce times)
Different period test range: 0.10ms~99ms, resolution: 0.01ms;
Internal trigger test range: 0.10ms~999ms, resolution: 0.01ms,
1000ms~9999ms, resolution: 0.1ms, 10000ms~200000ms resolution: 1ms.
External trigger test range: 0.01ms~200s
Accuracy rate within 1000ms: 0.05%±1 word
Speed measurement just opening (just closing) speed
Average speed in a specified time period (stroke period or angle period)
Speed measurement range 1mm sensor 0.01~25.00m/s,
0.1mm sensor 0.001~2.50m/s
345° angle sensor 0.01~25.00m/s,
Laser sensor 0.01~15.00m/s.
Stroke measurement moving contact stroke (stroke) (optional for 3-way stroke measurement)
Contact stroke (open distance)
Overtravel
Overshoot stroke or rebound stroke
Measuring range linear sensor: 50mm, measuring range: 0-50mm, resolution: 0.1mm.
Rotation sensor: 345о, measuring range: 0-1000mm, resolution: 0.08о. This sensor has an invalid area of 15 degrees, and the effective area of the sensor can be seen on the instrument when it is installed, and the value display is preferably about 160-200 degrees.
Acceleration sensor measuring range: 0-300mm, resolution: 0.1mm.
Coil current maximum current 20A, resolution: 0.01A
Measuring range of coil resistance 0~2000Ω, resolution: 0.01Ω
Instrument power supply AC220V ± 10%; 50Hz ± 10%
DC power output DC6~270V continuously adjustable, DC24V≤15A (short time), DC220V≤20A (short time)
External trigger voltage AC/DC10-300V, current ≤120A
Isolating switch measurement range Voltage output DC6~270V (adjustable)
Power output time 0.01-20 seconds (can be set)
maximum collection time of fracture signal 200 seconds
measurable fracture closing time, opening time, three-phase different period, bounce time and frequency
Host volume 440×300×260mm
Use environment -20℃~+50℃
Relative humidity ≤90%

 

Product Detail