| Power |
DC 14.8 V, 5200mAh rechargeable Li-Battery, approx. 16.8 V in fully charged status |
| Test Voltage |
250V, 500V, 1000V, 2500V, 5000V, 10kV |
| Voltage Measurement |
AC/DC up to 600V |
| Short Circuit Current |
≥5mA |
| Connections |
L terminal: High Voltage Terminal. Connect one end of the test leads to the L terminal, and the other end should be connected/clamped on to the device under test. |
| G terminal:Guard Terminal, it is used to provide a return path for surface leakage current and minimize its effect on the results. |
| E terminal:Earth Terminal, usually connected to the ground or neutral terminal of the measured object. |
| Time |
Max:99min and 99seconds, depending on the test method, adjustable |
| Resolution |
Insulation Resistance:0.01MΩ |
| Test Current:0.01nA |
| Test Voltage:0.1V |
| Capacitance:0.001μF |
| Backlight |
Adjustable backlight, high, medium, low brightness |
| Test Range |
Press the button to set |
| LCD |
5.6 bit Color LCD |
| Test Indication |
While testing, an LED light will flash, and the buzzer will sound. |
| Charging Indication |
A red light indicates that charging is in process; a green light indicates that the battery is fully charged. |
| Over Measurement Range |
–OL– |
| Data Storage |
Data is automatically saved upon the completion of the test, up to 1000 sets of data, including the current test data, ambient |
| temperature, date and time and other information. |
| Data View |
Use the buttons to select Data View option on the homescreen, and use the arrows to browse through the data. |
| Automatic shut-down |
Instrument will automatically shut down without operation in 15 minutes. |
| Standard Test Leads |
1 red, 1 green and 1 black test lead with clip. |
| Battery Voltage |
Display the remaining battery in real time. Please charge in a timely manner when the battery is low. |
| No output voltage for testing when the battery is low. |
| Date |
Date is displayed at the top of the screen. |
| Ambient Temperature |
Ambient temperature is displayed at the top of the screen. |
| Dimensions |
320mm(L) ×240mm (W)×145mm(H) |
| Weight |
Approximately 3.25kg (battery included) |
| Data Transmission |
Download data through the USB port |
| Communication Interface |
USB port, the saved data can be uploaded to the computer for saving or printing. |
| Communication Lines |
USB cable,1.5m in length |
| Working Temperature and Humidity |
-10℃~40℃;no condensations when below 80% RH |
| Storage Temperature and Humidity |
-20℃~60℃; no condensation when below 70% RH, |
| Withstand Voltage |
AC 5kV 50Hz ,1min between test leads and the cabinet |
| Dielectric Strength |
Above 500 MΩ between the test leads and the cabinet. |
| EMC |
IEC61326(EMC) |
| Safety Standards |
CAT IV 600V |